13.2.2 Low-carbon energy use


Dokuz Eylül University · THE Sustainability Impact Ratings 2027 · Evidence page

13.2.2 Low-carbon energy use

Field Content
Indicator 13.2.2 Low-carbon energy use
THE data requested Total energy used in 2025 (GJ); total energy used from low-carbon sources in 2025 (GJ)
Metric 13.2 Low-carbon energy use (SDG 13 Climate Action)

1. Statement

In calendar year 2025, Dokuz Eylül University (DEU) reported a total energy consumption of 131,337 GJ (36,482,512 kWh), excluding the DEU Research and Application Hospital. Low-carbon energy generation and utilization amounted to 92,830 GJ (25,786,033 kWh), corresponding to 70.7% of the reported total. This includes solar photovoltaic electricity generation accounted for through a grid-based offsetting mechanism (87,189 GJ), direct geothermal heat utilization (5,638 GJ) and on-campus wind electricity generation (3.3 GJ).

2. Definitions applied

  • Total energy used. All energy consumed by the University in calendar year 2025, whether generated on site or purchased, across all educational, research and administrative campuses (719,993 m² indoor floor area, including the Faculty of Medicine), excluding the DEU Research and Application Hospital (101,056 m²). This comprises grid electricity, natural gas for heating, hot water and kitchens, geothermal heat directly utilized on campus, and rooftop wind electricity.
  • Low-carbon energy. Solar photovoltaic electricity generated across six campuses (15.2 MWe installed capacity) and credited against institutional electricity consumption via grid-based offsetting, geothermal heat directly utilized at the 15 Temmuz Health and Arts Campus, and wind electricity generated and used at the Science and Technology Research and Application Centre (TEAM).
  • Excluded from low-carbon energy and organizational boundary. Fossil fuels; forest-derived biomass, which the University does not use on any campus; and biodiesel produced by a licensed recycler from the University’s waste vegetable oil (5,125 kg in 2025–2026), because this biodiesel is used outside the University. In addition, the energy consumption of the DEU Research and Application Hospital is excluded from the institutional boundary because it operates as a regional tertiary healthcare facility with a clinical energy profile distinct from core education and research activities.
  • Unit. Gigajoules (GJ), using 1 kWh = 0.0036 GJ. Natural gas is converted from cubic metres to kWh using the calorific value on supplier invoices. Figures are rounded to the nearest GJ.

3. Data for calendar year 2025

Energy stream Quantity 2025 Unit GJ
Electricity coming from the grid (all campuses excluding the hospital) 17,468,599 kWh 62,887
Solar PV electricity generated and going to the grid 24,219,130 kWh 87,189
Wind turbine electricity 913 kWh 3.3
Geothermal heat (15 Temmuz Campus) 1,565,990 kWh 5,638
Natural gas (all campuses excluding the hospital) 17,447,010 kWh 62,809
Total energy used 36,482,512 kWh 131,337
Total low-carbon energy used 25,786,033 kWh 92,830

Total energy consumption was calculated based on electricity and natural gas consumption, together with geothermal energy directly utilized by the University, excluding the university hospital. Solar PV generation was not added to total energy consumption, as the electricity generated is supplied to the national grid rather than directly consumed on campus.

However, solar PV generation is reported as part of DEU’s low-carbon energy contribution through the statutory grid-based electricity offsetting (mahsuplaşma) mechanism under Türkiye’s Electricity Market Unlicensed Electricity Generation Regulation (EPDK), whereby renewable electricity fed into the distribution grid is netted monthly against the University’s electricity consumption within the same distribution zone. Geothermal energy and wind turbine electricity are included in both total energy consumption and low-carbon energy utilization, as they are directly consumed on campus.

Total energy consumption (kWh) = Electricity consumption + Natural gas consumption + Geothermal energy utilized + Wind turbine electricity generation

= 17,468,599 + 17,447,010 + 1,565,990 + 913 = 36,482,512 kWh = 131,337 GJ

Total low-carbon energy generation and utilization (kWh) = Solar PV generation + Geothermal energy utilized + Wind electricity generation

= 24,219,130 + 1,565,990 + 913 = 25,786,033 kWh = 92,830 GJ

4. Cross-check with published figures

The University’s 2025–2026 sustainability report (May 2025–April 2026, excluding the hospital) gives the following values. They are shown here only to cross-check the order of magnitude of the calendar-year figures.

Item kWh GJ (calculated)
Electricity use, academic and administrative units 27,180,185 97,849
Natural gas use 21,968,037 79,085
Geothermal energy 1,943,670 6,997
Total energy use (excluding hospital) 51,091,892 183,931
Solar PV generation 24,110,405 86,797
Low-carbon energy (solar + geothermal + wind) 26,054,988 93,798
Low-carbon share — 51.0 %
Hospital electricity (not included above) 18,860,704 67,899

Note: The figures submitted to the THE portal are the calendar-year 2025 values in Section 3 (131,337 GJ total energy used and 92,830 GJ low-carbon energy used, corresponding to a 70.7% low-carbon share excluding the hospital, matching SDG 7 Indicators 7.3.1 and 7.5.1), whereas the table above provides the May 2025–April 2026 UI GreenMetric reporting period cross-check.

5. Verification

Responsible units: Department of Construction and Technical Works (Energy Management Unit and building energy managers); Zero Waste and Environmental Management Coordination Office; Sustainability Office. Contact: greencampus@deu.edu.tr; yapiteknik@deu.edu.tr. Primary records: utility invoices, ENVER portal entries, monthly solar PV and geothermal generation meter records, and the 2025 greenhouse gas inventory. Last reviewed: 8 November 2026.

6. References

Dokuz Eylül University Sustainability Office. (2026). 2025 greenhouse gas emissions calculation. https://greencampus.deu.edu.tr/wp-content/uploads/2026/01/2025-CO2.pdf

Dokuz Eylül University Sustainability Office. (n.d.). Enerji ve iklim değişikliği [Energy and climate change]. Retrieved October 21, 2026. https://greencampus.deu.edu.tr/tr/yesil-yerleske/enerji-ve-iklim-degisikligi/

Times Higher Education. (2026). THE Sustainability Impact Ratings methodology 2027 (Version 1.2), SDG 13, pp. 149–150.

Dokuz Eylül University. (2026). Dokuz Eylül University sustainability report 2025–2026. https://greencampus.deu.edu.tr/tr/surdurulebilirlik-hakkinda/deu-surdurulebilirlik-raporu/