7.2.5 Energy wastage identification


Dokuz Eylül University · THE Sustainability Impact Ratings 2027 · Evidence page

7.2.5 Energy wastage identification

Field Content
Indicator 7.2.5 Energy wastage identification
THE question Undergo energy reviews to identify areas where energy wastage is highest
Metric 7.2 University measures towards affordable and clean energy (SDG 7 Affordable and Clean Energy)

1. Statement

Dokuz Eylül University undergoes energy reviews to identify the areas where energy waste is highest. Under the Energy Efficiency Law No. 5627, energy audits (energy survey reports) have been carried out for the University’s buildings, every building holds an Energy Performance Certificate, and building energy managers review consumption data in the national ENVER portal. The findings are used to decide which buildings and systems are renovated first.

2. Types of energy review

2.1. Energy audits under Law No. 5627

Public buildings with a total construction area of at least 10,000 m² or an annual energy consumption of 250 tonnes of oil equivalent (TOE) or more must appoint energy managers and have periodic energy audits carried out under Law No. 5627. DEU has completed comprehensive Energy Survey Report (Enerji Verimliliği Etüt Raporu), energy management and Energy Performance Certificate projects for its buildings within this statutory framework. The most recent multi-campus Energy Survey Report, prepared by the accredited energy audit company İstanbul Enerji Sanayi ve Ticaret A.Ş. (certified audit specialists BEP 348, BEP 397, BEP 402 and BEP 561; field measurements completed in 2023 using 2020–2022 baseline data and published on the DEU Green Campus portal in November 2024), evaluated the building automation, HVAC, pumping, lighting and envelope systems across eight campuses using calibrated diagnostic instruments (Testo 470 tachometer for motor RPM, Handheld TUF2000H ultrasonic flowmeter for heating/cooling pump flow rates, Testo 435-4 multi-function analyser for lux levels and wall thermal transmittance U-values, and Hobo MX1102 CO₂ logger). Its main findings identified four priority areas where energy wastage was highest: (1) uninsulated valves, pumps and flanges in boiler rooms and mechanical heating circuits (quantified via ISO 12241 heat-loss calculations and addressed through TS-12241 glass-wool insulation jackets with at least 30 mm overlap); (2) legacy IE1 efficiency-class electric motors in heating, cooling and circulation pumps (prioritised for scheduled replacement with IE3 Premium Efficiency motors and variable-speed drives); (3) non-LED fluorescent luminaires (where electricity accounted for 23.7% of audited facility energy volume but 78.8% of total energy expenditure, driving campus-wide LED and motion-sensor retrofits); and (4) older chillers, steam/boiler units and building envelope thermal bridges/air infiltration (where natural gas accounted for 76.3% of thermal energy demand).

2.2. Energy Performance Certificates for all buildings

All university buildings hold a valid Energy Performance Certificate. Each certificate rates the building’s energy demand, insulation and the efficiency of its heating and cooling systems. The University uses these ratings to identify the buildings with the poorest performance.

2.3. Continuous review of consumption data

  • ENVER portal: building energy managers record the annual energy consumption of each campus building in the Energy Efficiency Portal of the Ministry of Energy and Natural Resources. Consumption trends are compared year on year to detect buildings with unusual increases.
  • Metering and SCADA: electricity, natural gas and water consumption are followed by the energy managers. In 2025 the Central Campus SCADA system was improved and the TR14, TR21 and TR23 reactive power compensation panels were renewed (Campus Infrastructure project 2025H03-259110).
  • ISO 50001:2018 Energy Management System: within the certified scope (administrative services of the Rectorate), the energy review identifies significant energy uses and improvement opportunities each year.

2.4. Physical inspections

The Department of Construction and Technical Works periodically inspects doors and windows for air leakage and repairs them, checks the insulation of heating pipes and ducts, vents heating lines and replaces faulty valves. Natural gas installations and air-conditioning units are inspected to prevent leaks.

2.5. Earlier building-level audits

Under the İklim-DE project (2017–2020, co-funded by the Ministry of Environment and Urbanisation and the European Union), detailed energy efficiency and CO₂ emission audits were carried out for the Faculty of Engineering and the Faculty of Business, an energy efficiency assessment was presented for the DEPARK technology development zone, and Energy Performance Certificates were issued for the faculty buildings. The audit reports remain publicly available on the Sustainability Office website.

3. How the findings are used

Areas identified as wasteful are addressed through the University’s major renovation and maintenance programme. Examples of measures delivered in 2025 include:

  • Replacement of two chiller units in the Faculty of Law and Vocational School of Justice building.
  • Conversion of fan-coil units to radiators in the Lecturers’ Building and separation of its air-conditioning circuits.
  • Renewal of the operating theatre chiller group and of the radiology and nuclear medicine air handling units at the University Hospital.
  • Replacement of fluorescent lighting with LED fittings during renovations, and fitting of variable-speed pumps in heating and cooling systems.

4. Key figures

Item Value Year Source
Campuses covered by the latest Energy Survey Report 8 2023–2024 (published Nov 2024) DEU Sustainability Report 2025–2026
Buildings with a valid Energy Performance Certificate All qualifying buildings across 19 campuses (17 BMS smart buildings, 236,009 m²) 2025 DEU Sustainability Report 2025–2026
Indoor floor area covered 821,049 m² 2025 DEU Sustainability Report 2025–2026
Spending on the major renovation programme TRY 65,936,992 2025 2025 Administrative Activity Report

5. Monitoring and verification

Implementation is monitored through the University’s Integrated Management System (quality, environment, food safety and energy) and the quality information system KALBİS, which records targets, actions and corrective actions in Plan-Do-Check-Act cycles. Results are published every year in the DEU Sustainability Report.

  • Responsible units: Department of Construction and Technical Works (Energy Management Unit and building energy managers); DEU Sustainability Office.
  • Contact: greencampus@deu.edu.tr; yapiteknik@deu.edu.tr
  • Last reviewed: 7 November 2026

6. References

Energy Efficiency Law No. 5627. (2007). Official Gazette of the Republic of Türkiye, No. 26510. https://www.mevzuat.gov.tr/mevzuat?MevzuatNo=5627&MevzuatTur=1&MevzuatTertip=5

Dokuz Eylül University Sustainability Office. (n.d.). Net zero target. Retrieved October 21, 2026, from https://greencampus.deu.edu.tr/net-zero-target/

Dokuz Eylül University Sustainability Office. (2026a). Dokuz Eylül University sustainability report 2025–2026. https://greencampus.deu.edu.tr/about-sustainability/deu-sustainability-report

Dokuz Eylül University Strategy Development Department. (2026). Dokuz Eylül Üniversitesi 2025 yılı idare faaliyet raporu [2025 administrative activity report]. https://strateji.deu.edu.tr/wp-content/uploads/2026/03/Dokuz-Eylul-Universitesi-2025-Yili-Idare-Faaliyet-Raporu.pdf

Dokuz Eylül University Sustainability Office. (n.d.). İklim-DE awareness project. Retrieved October 21, 2026, from https://greencampus.deu.edu.tr/tr/iklim-de-farkindalik-projesi/

Dokuz Eylül University Sustainability Office. (2026b). Energy and climate change. Retrieved October 21, 2026, from https://greencampus.deu.edu.tr/tr/yesil-yerleske/enerji-ve-iklim-degisikligi/

Dokuz Eylül University Sustainability Office. (2024, November). Dokuz Eylül Üniversitesi enerji verimliliği etüt raporu [Energy audit reports for eight campuses, prepared by İstanbul Enerji Sanayi ve Ticaret A.Ş.]. https://greencampus.deu.edu.tr/wp-content/uploads/2024/11/EnergyAuditReports.pdf