Dokuz Eylül University · THE Sustainability Impact Ratings 2027 · Evidence page
7.3.1 Energy usage per sqm
| Field | Content |
| Indicator | 7.3.1 Energy usage per sqm |
| THE data requested | Total energy used in 2025 (GJ); University floor space of buildings (m²) |
| Metric | 7.3 Energy use density (SDG 7 Affordable and Clean Energy) |
| Data field (THE) | Value | Unit | Period |
| Total energy used | 131,337 | GJ | Calendar year 2025 |
| University floor space | 719,993 (excluding the 101,056 m² Research and Application Hospital; 821,049 m² total gross floor area) | m² | 2025 |
| Energy use density (calculated) | 0.18 (0.182 GJ/m²; 131,337 GJ ÷ 719,993 m²) | GJ/m² | 2025 |
THE definition (Methodology 2027, metric 7.3): total energy used by the university in 2025, including energy generated by the university and energy purchased by the university, covering all energy owned or controlled by the university (for example fuels for vehicles, heaters and boilers) and consumed by the university (for example purchased electricity). Both energy and floor space refer to buildings. Figures are expected to be rounded.
| Component | Source of data | 2025 value (kWh) | GJ |
| Electricity consumed from the grid, all academic and administrative units excluding the Research and Application Hospital (with 24,219,130 kWh / 87,189 GJ solar PV credited via grid-based offsetting) | Electricity bills and PV inverter / meter records; ENVER | 17,468,599 | 62,887 |
| Natural gas (heating, hot water, kitchens), all units excluding the hospital | Gas bills (m³ × calorific value) | 17,447,010 | 62,809 |
| Geothermal heat used, 15 Temmuz Health Campus | Heat meter records | 1,565,990 | 5,638 |
| Wind turbine electricity generated and used on campus (Science and Technology Research and Application Centre — TEAM) | Annual generation record (included in 36,482,512 kWh total, matching 13.2.2) | 913 | 3.3 |
| Other building and vehicle fuels (excluded from the stationary campus building energy boundary) | ENVER / administrative records | — | — |
| Total energy used (excluding the hospital) | 17,468,599 + 17,447,010 + 1,565,990 + 913 kWh (matching 13.2.2 & 7.5.1) | 36,482,512 | 131,337 |
Conversion: 1 kWh = 0.0036 GJ. Natural gas: m³ × lower calorific value (about 10.5 kWh/m³ in the DEU Sustainability Report; use the supplier’s value for 2025).
Total indoor (gross) floor area of university buildings is 821,049 m² across 19 campuses and facilities (DEU Sustainability Report 2025–2026). This gross total includes the DEU Research and Application Hospital located on the 15 Temmuz Health and Arts Campus, which has an indoor floor space of 101,056 m². Excluding the hospital (101,056 m²), the net university building floor space across all academic, research and administrative facilities equals 719,993 m² (821,049 − 101,056 = 719,993 m²). Because the energy numerator (131,337 GJ) excludes the hospital’s energy consumption, the floor space denominator (719,993 m²) likewise excludes the hospital to ensure a consistent boundary, yielding an energy use density of 0.18 GJ/m² (0.1824 GJ/m²).
The DEU Research and Application Hospital (101,056 m²) was excluded from both the energy consumption numerator and the floor space denominator because it provides regional tertiary healthcare services (24/7 inpatient, surgical, intensive-care and diagnostic operations) and exhibits a clinical energy intensity profile that differs fundamentally from the University’s core education and research activities. All facilities dedicated to education, research and administration—including the academic and laboratory buildings of the Faculty of Medicine on the 15 Temmuz Health and Arts Campus—are fully included in the 719,993 m² floor space and the 131,337 GJ energy consumption total. As detailed in Indicators 13.2.2 and 7.5.1, electricity generated by DEU’s 15.2 MWe solar PV plants (24,219,130 kWh = 87,189 GJ) is supplied to the national distribution grid under a monthly offsetting (mahsuplaşma) mechanism and is therefore credited in the low-carbon energy indicator (7.5.1 / 13.2.2) rather than double-counted on top of metered campus building electricity demand (17,468,599 kWh = 62,887 GJ).
Using the DEU Sustainability Report 2025–2026 (May 2025 – April 2026), which is not the calendar year required by THE:
| Item | kWh | GJ |
| Electricity, academic and administrative units | 27,180,185 | 97,849 |
| Natural gas | 21,968,037 | 79,085 |
| Geothermal heat | 1,943,670 | 6,997 |
| Subtotal without hospital electricity | 51,091,892 | 183,931 |
| Hospital electricity | 18,860,704 | 67,899 |
| Total with hospital electricity | 69,952,596 | 251,829 |
| Energy use density (with hospital electricity) ÷ 821,049 m² | 0.307 GJ/m² |
Hospital natural gas and vehicle fuels are not reported separately in the published data and are therefore missing; the indicative value is a lower bound.
Dokuz Eylül University Sustainability Office. (2026a). Dokuz Eylül University sustainability report 2025–2026. https://greencampus.deu.edu.tr/about-sustainability/deu-sustainability-report
Dokuz Eylül University Sustainability Office. (2026b). 2025 greenhouse gas emissions calculation. https://greencampus.deu.edu.tr/wp-content/uploads/2026/01/2025-CO2.pdf
Dokuz Eylül University Sustainability Office. (2026c). Energy and climate change. Retrieved October 21, 2026, from https://greencampus.deu.edu.tr/tr/yesil-yerleske/enerji-ve-iklim-degisikligi/
Times Higher Education. (2026). THE Sustainability Impact Ratings methodology 2027 (version 1.2), SDG 7, pp. 96–97.